KEY FEATURES
- Rate Of Rise cum Fix Temperature type
- Dual LED for 360 degree visibility
- 2 wire based detector
- Advance algorithms provides advanced detection discrimination
- Easy installation
- Low maintenance
- High immunity against unwanted alarms
- Stable heat chamber, No adjustment or replacement required
TECHNICAL DATA
- Operating Voltage DC (10.8 ~ 30) V
- Frequency 3-5 Seconds
- Heat Sensitivity 135° F/ROR
- Reset Voltage Less than 1 volt
- Reset time Less than 1 sec.
- Alarm indication 2 continuous emitting red LEDs
- Start up current 100 μA
- Alarm current (Max) 50 mA
- Stand by current 45 μA